Please note: The XYCD-60 is a widely manufactured generic temperature controller. While this guide covers the standard hardware and functionality, specific wire color codes or port layouts may vary slightly between production batches. Always verify the markings on your specific device's terminal blocks before final wiring. The XYCD-60 is a dual-display, dual-output temperature controller. It is commonly used in incubators, refrigeration units, fermentation chambers, and industrial heating/cooling applications. Its primary feature is the ability to control two separate processes simultaneously or control a single process with both heating and cooling mechanisms. G-queen.13.08.15.mumo.girls.summer.games.2013.b...: Me Of
| Code | Function | Description | Range/Default | | :--- | :--- | :--- | :--- | | | Heating / Cooling Mode | Sets the relay to activate on temperature drop (Heating) or rise (Cooling). | H (Heating) / C (Cooling) | | P1 | Hysteresis (Dead Band) | The difference between stopping and starting. If set to 2.0°C, the relay activates at Set Temp - 2°C (Heating mode). | 0.1°C – 15.0°C | | P2 | Delay Protection | Prevents rapid cycling of compressor/relay. (e.g., wait 3 minutes before restarting). | 0 – 10 Minutes | | P3 | High Alarm | Audible alarm triggers if temp exceeds this limit. | Off / Temp Value | | P4 | Low Alarm | Audible alarm triggers if temp drops below this limit. | Off / Temp Value | | P5 | Calibration | Corrects sensor reading errors. If actual temp is 25°C and display shows 24°C, set P5 to +1.0. | -5.0°C to +5.0°C | Historia Medieval Ii Siglos Xiiixv Pdf Review